Southwire 67430202, Metal Clad Cable 10 AWG 4C 4 Neutrals with Ground Solid Copper THHN
Description
Southwire 67430202 is an Armorlite® Type MC neutral-per-phase cable with four 10 AWG solid copper THHN/THWN phase conductors in black, red, blue and pink and four 10 AWG neutrals in white-black, white-red, white-blue and white-pink, plus a green insulated ground conductor, under aluminum interlocked armor. Conductors rated 90°C dry as Type THHN/THWN.
Southwire 67430202 Technical Specs
Conductors and Insulation
| Conductor Size | 10 AWG |
|---|---|
| Phase Conductors | 4 (Black, Red, Blue, Pink) |
| Neutral Conductors | 4 x 10 AWG (White-Black, White-Red, White-Blue, White-Pink) |
| Grounding Conductors | 1 x 10 AWG (Green) |
| Conductor | Solid copper per ASTM B3 |
| Insulation | Polyvinyl chloride with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 25 mils (0.64 mm) |
| Diameter Over Conductor | 0.101 in (0.26 cm) |
Grounding and Armor
| Grounding Conductor | Green polyvinyl chloride with nylon sheath Type THHN/THWN insulated ground conductor |
|---|---|
| Binder | Mylar tape; binder tape with print legend wrapped around assembly |
| Armor | Aluminum interlocked armor |
Dimensions and Weight
| Diameter Over Armor | 0.823 in (2.09 cm) |
|---|---|
| Approximate Weight | 425 lbs per 1,000 ft (632 kg/km) |
Ratings
| Conductor Temperature Rating | 90°C dry, Type THHN/THWN |
|---|---|
| Location | Dry, indoor locations only per NEC 330.10(A)(10) (unjacketed) |
Standards and Compliance
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1569 | Metal-Clad Cables |
| UL 1479 | Standard for Safety Fire Tests of Penetration Firestops |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Meets or Exceeds | Federal Specification A-A59544 (formerly J-C-30B); NFPA 70 (National Electrical Code), Article 330 |
Neutral-per-phase construction for installation and marking of neutral conductors under NEC 200.4. Neutrals are not to be used for more than one circuit (branch, multi-wire branch or ungrounded feeder); see NEC 200.4 for complete requirements.
Southwire 67430202 Applications
- Circuits affected by harmonics from non-linear switching loads such as computers, variable frequency drives, electrical test equipment and office equipment.
- Multiple circuits for branch, feeder and service power distribution in commercial, industrial, institutional and multi-residential buildings.
- Fishing through or embedding in plaster.
- Concealed or exposed runs.
- Environmental air-handling spaces per NEC 300.22(C).
- Places of assembly per NEC 518.4 and theaters per NEC 520.5.
- Cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) and 645.5(D)(2).
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.