Southwire 67740099, Power Tray Cable 750 kcmil 3C Aluminum Alloy THHN TC-ER 600V Black
Description
Southwire 67740099 is a 750 kcmil, 3-conductor Type TC-ER power tray cable rated 600V, with compact stranded 8000 Series aluminum alloy conductors in PVC with nylon layer Type THHN insulation, one 3/0 AWG aluminum alloy grounding conductor and a black polyvinyl chloride (PVC) jacket.
Southwire 67740099 Technical Specs
Construction
| Conductor Size | 750 kcmil |
|---|---|
| Number of Conductors | 3, plus one grounding conductor |
| Conductor | Class B compact stranded 8000 Series aluminum alloy per ASTM B800 and ASTM B836 |
| Strands per Conductor | 58 |
| Insulation | Polyvinyl chloride (PVC) with nylon layer, Type THHN |
| Conductor Identification | Numbered conductors (1, 2, 3) per ICEA S-58-679 Method 4 |
| Grounding Conductor | One 3/0 AWG Class B compact stranded 8000 Series aluminum alloy |
| Filler | Paper |
| Binder | Polyester flat thread binder tape |
| Jacket | Polyvinyl chloride (PVC) |
| Jacket Colour | Black |
| Type Designation | TC-ER |
| Silicone | Silicone free |
Dimensions and Weight
| Diameter Over Conductor | 0.908 in (2.31 cm) |
|---|---|
| Insulation Thickness | 70 mils (1.78 mm) |
| Jacket Thickness | 110 mils (2.79 mm) |
| Approx. Overall Diameter | 2.522 in (6.41 cm) |
| Aluminum Weight | 2300 lbs/1000 ft (3423 kg/km) |
| Approx. Total Weight | 3580 lbs/1000 ft (5328 kg/km) |
Electrical and Thermal Ratings
| Voltage Rating | 600V |
|---|---|
| Conductor Temperature | 75°C in wet locations, 90°C in dry locations; 105°C emergency overload; 250°C short circuit |
Standards and Compliance
| ASTM B801 | Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy |
|---|---|
| ASTM B836 | Compact Rounded Stranded Aluminum Conductors |
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1277 | Electrical Power and Control Tray Cables |
| UL 1685 | Vertical-Tray Fire Propagation and Smoke Release Test |
| ICEA S-58-679 | Control Cable Conductor Identification Method 4 |
Southwire 67740099 Applications
- Wet and dry areas, conduits, ducts, troughs, cable trays and direct burial.
- Aerial installation supported by a messenger.
- Class I, II and III, Division 2 per NEC Article 501 and 502.
- Exposed runs (TC-ER) per NEC 336.10.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.