Southwire 67753299, Machine Flex Power Tray Cable 18 AWG 9C Copper TC-ER Black
Description
Southwire 67753299 is an 18 AWG, 9-conductor Machine Flex flexible power tray cable with Class K flexible stranded bare annealed copper conductors, PVC with nylon layer insulation and a black thermoplastic elastomer (TPE) jacket. One of the 9 conductors is a green ground with a yellow stripe. Type designation TC-ER/WTTC/ITC/PLTC/MTW.
Southwire 67753299 Technical Specs
Construction
| Conductor Size | 18 AWG |
|---|---|
| Number of Conductors | 9, including one green/yellow ground |
| Conductor | Class K flexible stranded bare annealed copper per ASTM B3, B172 and B174 |
| Strands per Conductor | 16 |
| Insulation | Polyvinyl chloride (PVC) with nylon layer |
| Conductor Identification | Numbered conductors per ICEA S-58-679 Method 4 (1 to 8), plus the green/yellow ground |
| Grounding Conductor | One green ground with yellow stripe, counted among the conductors |
| Jacket | Thermoplastic elastomer (TPE) |
| Jacket Colour | Black |
| Type Designation | TC-ER/WTTC/ITC/PLTC/MTW |
| Cold Impact Rating | -40°C |
Dimensions and Weight
| Diameter Over Conductor | 0.044 in (0.11 cm) |
|---|---|
| Insulation Thickness | 20 mils (0.51 mm) |
| Jacket Thickness | 45 mils (1.14 mm) |
| Approx. Overall Diameter | 0.411 in (1.04 cm) |
| Minimum Bend Radius | 1.6 in (4.06 cm) |
| Copper Weight | 45 lbs/1000 ft (67 kg/km) |
| Approx. Total Weight | 102 lbs/1000 ft (152 kg/km) |
Electrical and Thermal Ratings
| Conductor Temperature | 75°C in wet locations, 90°C in dry locations; 130°C emergency overload; 150°C short circuit |
|---|---|
| AC Resistance at 75°C (ohms/1000 ft) | 8.613 |
| Allowable Ampacity, Raceway, 90°C | 9 A |
Standards and Compliance
| ASTM B172 | Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors |
|---|---|
| ASTM B174 | Bunch-Stranded Copper |
| UL 13 | Power-Limited Circuit Cables |
| UL 66 | Fixture Wire |
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1277 | TC-ER |
| UL 2250 | Instrumentation Tray Cable |
| UL 2277 | Type WTTC |
| CSA C22.2 No.230 | Tray Cables - Rated TC |
| CSA C22.2 No. 239 | Control and instrumentation cables |
| ICEA S-58-679 | Control Cable Conductor Identification Method 4 |
| ICEA S-95-658 (NEMA WC70) | Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| Ecolab PM-40-1 | Exceeds the Material Resistance Test With 30-day Exposure, UL Verified V747862 |
| NFPA 79 | Electrical Standard for Industrial Machinery |
| CE/RoHS-2 | CE Marking applied solely to express conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive |
| Made in America | Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661 |
Southwire 67753299 Applications
- Wet and dry areas, conduits, ducts, troughs, cable trays and direct burial, conforming to NFPA 79.
- Class I, II, Division 2 per NEC Article 501 and 502.
- Exposed runs (TC-ER) per NEC 336.10.
- Powering CNC machines, grinding, cutting, metal forming and buffing equipment.
- Bottling equipment, conveyors, processing and packaging equipment, assembly lines and control panels.
- Food and beverage, oil sands, plant expansion, wind energy and data centers.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.