Southwire 67755499, Metal Clad Cable 10 AWG 6C Neutral Per Phase Stranded Copper THHN
Description
Southwire 67755499 is an Armorlite® Type MC neutral-per-phase cable with six 10 AWG 19-strand copper THHN/THWN phase conductors, six 10 AWG neutrals and a 10 AWG green insulated ground under aluminum interlocked armor, with phase identification: 13 wires in all. Its conductors are rated 90°C dry.
Southwire 67755499 Technical Specs
Conductors and Insulation
| Conductor Size | 10 AWG |
|---|---|
| Phase Conductors | 6 |
| Neutral Conductors | 6 x 10 AWG |
| Conductor | 19-strand class C compressed copper per ASTM B8 |
| Stranding | 19-strand |
| Insulation | Polyvinyl chloride with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 25 mils (0.64 mm) |
| Diameter Over Conductor | 0.117 in (0.30 cm) |
Grounding and Armor
| Grounding | Green insulated ground, PVC with nylon sheath Type THHN/THWN, 10 AWG |
|---|---|
| Ground Size | 1x10 |
| Binder | Mylar tape, with print legend wrapped around the assembly |
| Armor | Aluminum interlocked armor |
Dimensions and Weight
| Diameter Over Armor | 0.929 in (2.36 cm) |
|---|---|
| Approximate Weight | 637 lbs per 1,000 ft (948 kg/km) |
Ratings
| Temperature Rating | 90°C dry (Type THHN/THWN) |
|---|
Standards and Compliance
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
|---|---|
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1569 | Metal-Clad Cables |
| UL 1479 | Standard for Safety Fire Tests of Penetration Firestops |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Meets or Exceeds | Federal Specification A-A59544 (formerly J-C-30B); NFPA 70 (National Electrical Code), Article 330 |
Southwire 67755499 Applications
- Neutral-per-phase construction that complies with NEC 200.4 for the installation and marking of neutral conductors; a neutral is not to be used for more than one circuit (branch, multiwire branch or ungrounded feeder).
- Circuits affected by harmonics from non-linear switching loads such as computers, variable frequency drives, electrical test equipment and office equipment.
- Multiple circuits for branch, feeder and service power distribution in commercial, industrial, institutional and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22(C).
- Places of assembly per NEC 518.4 and theaters per NEC 520.5.
- Cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) and 645.5(D)(2).
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.