Southwire 67781805, Building Wire 350 kcmil Stranded Copper T90/TWN75/THHN/MTW Black
Description
Southwire 67781805 is a 350 kcmil single-conductor SIMpull building wire in black, with 37-strand copper and PVC insulation with a nylon sheath. It carries the T90/TWN75/THHN/MTW type designations and a maximum voltage rating of 600 volts.
Southwire 67781805 Technical Specs
Conductor & Dimensions
| Conductor Size | 350 kcmil |
|---|---|
| Conductor Material | Copper |
| Number of Conductors | 1 |
| Strands | 37 |
| Diameter Over Conductor | 0.661 in (1.68 cm) |
| Insulation | Polyvinyl chloride (PVC) with nylon sheath |
| Insulation Thickness | 60 mils (1.52 mm) |
| Insulation Colour | Black |
| Approx. Outside Diameter | 0.783 in (1.99 cm) |
| Copper Weight | 1,080 lbs/1000 ft (1,607 kg/km) |
| Approx. Weight | 1,164 lbs/1000 ft (1,732 kg/km) |
Ratings
| Voltage Rating | 600 V |
|---|---|
| Type Designations | T90, TWN75, THHN, MTW |
| T90 Nylon Temperature | Dry locations, not exceeding 90°C |
| TWN75 Temperature | Wet or dry locations, not more than 75°C |
| THHN Temperature | Dry locations, not exceeding 90°C; Gasoline and Oil Resistant II applications, not exceeding 75°C |
| MTW Temperature | Dry locations, not exceeding 90°C; wet locations and Gasoline and Oil Resistant II applications, not exceeding 60°C |
| Minimum Installation Temperature | -25°C |
| Minimum Operating Temperature | -40°C |
Compliance & Standards
| Standards | CSA FT-1 Flame Test; Canadian Electrical Code |
|---|
Southwire 67781805 Applications
- As T90 Nylon, intended for installation in conduit (raceways) as exposed wiring in dry locations.
- Its TWN75 designation covers wet or dry locations within the 75°C limit given above.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.