Southwire 67927299, Building Wire 3/0 AWG Copper SIMpull THHN-THWN-2 MTW Pink
Description
Southwire 67927299 is a 3/0 AWG copper SIMpull THHN-THWN-2 MTW building wire in pink. Its 19-strand combination-unilay bare copper conductor is insulated with heat and moisture resistant PVC under a nylon sheath utilizing SIMpull Technology, which lets it install without a pulling lubricant. Rated 600 volts for all applications.
Southwire 67927299 Technical Specs
Construction
| Conductor Size | 3/0 AWG |
|---|---|
| Conductor Material | Class B combination-unilay stranded, soft drawn annealed bare copper per ASTM B787 |
| Number of Strands | 19 |
| Insulation | Heat and moisture resistant PVC |
| Sheath | Nylon, utilizing SIMpull Technology |
| Type Designation | THHN-THWN-2 MTW |
| Insulation Colour | Pink |
Dimensions and Weight
| Diameter Over Conductor | 0.456 in (1.16 cm) |
|---|---|
| Insulation Thickness | 50 mils (1.27 mm) |
| Nylon Sheath Thickness | 5 mils (0.13 mm) |
| Approx. Overall Diameter | 0.574 in (1.46 cm) |
| Copper Content Weight | 518 lbs/1000 ft (771 kg/km) |
| Approx. Total Weight | 578 lbs/1000 ft (860 kg/km) |
Ratings
| Voltage | 600 volts, all applications |
|---|---|
| THHN | Dry locations, not to exceed 90°C |
| THWN-2 | Wet or dry locations, not to exceed 90°C, or 75°C when exposed to oil |
| MTW | Wet locations or exposed to oil, not to exceed 60°C; dry locations, not to exceed 90°C (ampacity limited to that for 75°C conductor temperature per NFPA 79) |
Features
| Sunlight | Sunlight resistant, #8 AWG and larger |
|---|---|
| Oil and Gasoline | Gasoline and Oil Resistant II |
| Cable Tray | CT Rated, 1/0 AWG and larger |
| Flame Tests | VW-1 and FT-1, all sizes |
| RoHS | Compliant |
Standards
| ASTM B787 | 19 Wire Combination Unilay-Stranded Copper Conductors |
|---|---|
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1063 | Machine Tool Wiring (MTW) |
| UL 1685 | Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger) |
| CSA C22.2 No. 75 | Thermoplastic Insulated Wires and Cables |
| ICEA S-95-658 (NEMA WC70) | Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
| Federal Specification | A-A-59544 |
| NMX-J-010-ANCE | Thermoplastic insulated wires and cables |
| NOM-063-SCFI | Electrical Products – Conductors – Safety Requirements |
| NEMA 70901-2-2024 | Make It American Compliance with Domestic Preference Requirements Pt. 2 Wire & Cable |
Southwire 67927299 Applications
- Pulled into conduit and cable trays for services, feeders and branch circuits in commercial or industrial applications, as specified in the National Electrical Code and other applicable codes and standards.
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.