Southwire 69005704, Metal Clad Cable 12 AWG 6C Multi-Circuit with Ground Solid Copper THHN
Description
Southwire 69005704 is an Armorlite® multi-circuit Type MC cable with six 12 AWG solid copper conductors, insulated Type THHN/THWN, and a green insulated ground, all under aluminum interlocked armor. Its conductors are rated 90°C dry; as unjacketed Type MC it is for dry, indoor locations only.
Southwire 69005704 Technical Specs
Conductors and Insulation
| Conductor Size | 12 AWG |
|---|---|
| Number of Conductors | 6, plus a grounding conductor |
| Conductor | Solid copper per ASTM B3 |
| Number x Neutral Size | 2x12 |
| Insulation | Polyvinyl chloride with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 20 mils (0.51 mm) |
| Diameter Over Conductor | 0.080 in (0.20 cm) |
Grounding and Armor
| Grounding Conductor | Green insulated ground conductor, polyvinyl chloride with nylon sheath, Type THHN/THWN |
|---|---|
| Ground Size | 1x12 |
| Binder | Mylar tape with print legend, wrapped around the assembly |
| Armor | Aluminum interlocked armor |
Dimensions and Weight
| Diameter Over Armor | 0.577 in (1.47 cm) |
|---|---|
| Approximate Weight | 211 lbs per 1,000 ft (314 kg/km) |
Ratings
| Conductor Temperature | 90°C dry (Type THHN/THWN) |
|---|---|
| Location | Dry, indoor locations only per NEC 330.10(A)(10) (unjacketed Type MC) |
Standards
| ASTM B3 | Soft or annealed copper wire |
|---|---|
| UL 83 | Thermoplastic insulated wires and cables |
| UL 1569 | Metal-clad cables |
| UL 1479 | Fire tests of penetration firestops |
| UL 1685 FT4 | Vertical-tray fire propagation and smoke release test |
| IEEE 1202 FT4 | Flame test (70,000) BTU/hr vertical tray test |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Federal Specification | Meets or exceeds A-A59544 (formerly J-C-30B) |
| NFPA 70 (NEC) | Meets or exceeds Article 330 |
Southwire 69005704 Applications
- Multiple circuits for branch, feeder and service power distribution in commercial, industrial, institutional and multi-residential buildings.
- Fished installations, or embedded in plaster.
- Concealed or exposed runs.
- Environmental air-handling spaces per NEC 300.22(C).
- Places of assembly per NEC 518.4 and theaters per NEC 520.5.
- Cable tray and approved raceways.
- Under raised floors, for information technology equipment conductors and cables per NEC 645.5(D) and 645.5(D)(2).
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.