Southwire 69377131, Bare Aluminum Conductor ACSS/TW 1272 KCMIL 39/19 PHEASANT
Description
Southwire 69377131 is an ACSS/TW bare overhead conductor in 1272 KCMIL, codeword PHEASANT, Type 13. Its 39 trapezoidal-shaped aluminum strands, drawn from 63% minimum average conductivity aluminum 1350-0 wire in the fully annealed (soft) temper, are stranded in layers around a steel core of 19 wires. Nominal outside diameter is 1260 mils and nominal total weight is 1630 lbs per 1000 ft. With the aluminum in soft temper, the steel core carries most or all of the mechanical load, and its wires are protected from corrosion by Galfan, a zinc-5% aluminum-mischmetal alloy coating.
Southwire 69377131 Technical Specs
Conductor
| Codeword | PHEASANT |
|---|---|
| Conductor Type | ACSS/TW (Aluminum Conductor, Steel Supported, Trapezoidal Shaped Aluminum Strands) |
| Southwire Designation | 1272-39/19 TYPE 13 ACSS/TW/MA2/63% PHEASANT |
| Design | Type 13 |
| Conductor Size | 1272 KCMIL |
| Stranding (Aluminum/Steel) | 39/19 |
| Aluminum Wire | 1350-0, 63% minimum average conductivity, fully annealed (soft) temper, trapezoidal shaped |
| Core Designation | MA2 |
Dimensions and Weight
| Nominal Outside Diameter | 1260 mils (32.00 mm) |
|---|---|
| Nominal Total Weight | 1630 lbs/1000 ft (2426 kg/km) |
Standards
Its ACSS/TW conductor meets or exceeds the following ASTM specifications.
| ASTM B500 | Metallic Coated Stranded Steel Core for Aluminum Conductors, Steel Reinforced |
|---|---|
| ASTM B609 | Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes |
| ASTM B802 | Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced |
| ASTM B803 | High-Strength Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Aluminum and Aluminum-Alloy Conductors, Steel Reinforced |
| ASTM B857 | Shaped Wire Compact Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Supported (ACSS/TW) |
Southwire 69377131 Applications
- ACSS/TW is for overhead distribution and transmission lines.
- The line is designed to operate continuously at elevated temperatures up to 250°C without loss of strength.
- Under emergency electrical loadings it sags less than ACSR/TW, and long-term creep of the aluminum does not affect its final sags.
- The construction also has excellent self-damping properties.
- For new line construction, design opportunities include reduced tower cost, decreased sag, increased operating temperature and improved corrosion resistance.
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.