Southwire 89014602, Building Wire 10 AWG Copper USE-2 RHH-RHW-2 Red
Description
Southwire 89014602 is a 10 AWG copper building wire carrying the USE-2 and RHH-RHW-2 designations, with red insulation. Its 7-strand annealed (soft) copper conductor is insulated with cross-linked polyethylene (XLP), high-heat and moisture resistant. Each designation is rated for a 90°C conductor temperature: RHH in dry locations, RHW-2 and USE-2 in wet or dry locations.
Southwire 89014602 Technical Specs
Construction
| Conductor Size | 10 AWG |
|---|---|
| Conductor | Annealed (soft) copper |
| Number of Strands | 7 |
| Insulation | Cross-linked polyethylene (XLP) |
| Type Designation | USE-2 RHH-RHW-2 |
| Insulation Colour | Red |
Dimensions and Weight
| Diameter Over Conductor | 0.113 in (0.29 cm) |
|---|---|
| Insulation Thickness | 45 mils (1.14 mm) |
| Approx. Overall Diameter | 0.203 in (0.52 cm) |
| Copper Content Weight | 32 lbs/1000 ft (48 kg/km) |
| Approx. Total Weight | 42 lbs/1000 ft (63 kg/km) |
Ratings
| USE-2 Temperature | 90°C in wet or dry locations |
|---|---|
| RHH Temperature | 90°C in dry locations |
| RHW-2 Temperature | 90°C in wet or dry locations |
Standards
| ASTM | B3 and B8 |
|---|---|
| UL 854 | UL Standard 854 for USE-2 |
| Federal Specification | A-A-59544 |
| National Electrical Code | NFPA 70 - 2011 Edition |
| NEMA WC 70 | Construction Requirements |
| RoHS/REACH | Compliant |
Southwire 89014602 Applications
- The Type USE-2 conductors is used with conduit as specified in the 2011 National Electrical Code.
- When used as Type USE-2, it is suitable as underground service entrance cable for direct burial at conductor temperatures not exceeding 90°C.
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.