Southwire 89052799, Armored Cable 8 AWG 4C Copper XHHW-2 600 V Black
Description
Southwire 89052799 is an 8 AWG four-conductor Type MC-HL ARMOR-X® armored cable rated 600 V. Its four 7-strand compressed copper conductors carry 45 mils of XHHW-2 XLPE, and one 10 AWG bare copper grounding conductor runs with them. ARMOR-X® continuous corrugated welded armor and a black polyvinyl chloride (PVC) outer jacket complete the cable.
Southwire 89052799 Technical Specs
Conductors & Insulation
| Conductor Size | 8 AWG |
|---|---|
| Number of Conductors | 4 |
| Strands per Conductor | 7 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Insulation | Cross-linked polyethylene (XLPE), Type XHHW-2 |
| Insulation Thickness | 45 mils (1.14 mm) |
| Conductor Colors | BLACK/RED/BLUE/ORANGE |
| Diameter Over Conductor | 0.141 in (0.36 cm) |
Grounding, Armor & Jacket
| Grounding Conductor | One 10 AWG Class B compressed stranded bare copper grounding conductor |
|---|---|
| Filler | Polypropylene |
| Binder | Polypropylene tape |
| Armor | ARMOR-X® continuous corrugated welded armor |
| Diameter Over Armor | 0.840 in (2.13 cm) |
| Outer Jacket | Black polyvinyl chloride (PVC) |
| Jacket Thickness | 50 mils (1.27 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 0.946 in (2.40 cm) |
|---|---|
| Approximate Weight | 476 lbs/1000 ft (708 kg/km) |
| Maximum Pull Tension | 422 lbs (191.42 kg) |
| Minimum Bend Radius | 6.6 in (16.76 cm) |
Ratings & Compliance
| Voltage Rating | 600 V |
|---|---|
| Type Designation | Type MC-HL |
| Operating Temperatures | 90°C normal operation in wet and dry locations; 130°C emergency overload; 250°C short circuit |
| Cold Bend | -50°C |
| Location Rating | Class I, II, and III, Division 1 and 2 per NEC Article 501, 502, and 503 |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; UL 44 Thermoset-Insulated Wires and Cables; UL 1569 Metal-Clad Cables; UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test; UL 2225 Cables and Cable-Fittings For Use In Classified Locations; ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE); ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy; IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr) |
Southwire 89052799 Applications
- Wet and dry areas, conduits, ducts, troughs and trays, along with direct burial and aerial runs supported by a messenger.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.