Southwire 89063689, Armored Cable 2 AWG 3C Copper 5 kV 133% / 8 kV 100% Yellow
Southwire · MPN 89063689
Description
Southwire 89063689 is a 2 AWG three-conductor Type MC-HL medium-voltage armored power cable rated 5 kV 133% / 8 kV 100%. Its three 7-strand bare copper conductors carry 115 mils of NL-EPR with semi-conducting conductor and insulation shields and a 5 mil copper tape shield, and three 10 AWG bare copper grounding conductors run with them. ARMOR-X® continuous corrugated welded aluminum armor and a yellow polyvinyl chloride (PVC) outer jacket complete the cable.
Southwire 89063689 Technical Specs
Conductors & Insulation
| Conductor Size | 2 AWG |
|---|---|
| Number of Conductors | 3 |
| Strands per Conductor | 7 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Insulation | No-lead ethylene propylene rubber (NL-EPR) |
| Insulation Thickness | 115 mils (2.92 mm) |
| Insulation Level | 133% |
| Diameter Over Conductor | 0.282 in (0.72 cm) |
| Diameter Over Insulation | 0.545 in (1.38 cm) |
Shielding
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape, 25% overlap |
| Diameter Over Shield | 0.605 in (1.54 cm) |
Grounding, Armor & Jacket
| Grounding Conductors | Three 10 AWG Class B compressed stranded bare copper grounding conductors |
|---|---|
| Filler | Wax paper |
| Binder | Polypropylene tape |
| Armor | ARMOR-X® continuous corrugated welded aluminum armor |
| Diameter Over Armor | 1.670 in (4.24 cm) |
| Outer Jacket | Yellow polyvinyl chloride (PVC) |
| Jacket Thickness | 70 mils (1.78 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 1.810 in (4.60 cm) |
|---|---|
| Approximate Weight | 1903 lbs/1000 ft (2832 kg/km) |
| Maximum Pull Tension | 1592 lbs (722.12 kg) |
| Minimum Bend Radius | 12.6 in (32.00 cm) |
Ratings & Compliance
| Voltage Rating | 5 kV 133% / 8 kV 100% |
|---|---|
| Type Designation | Type MC-HL |
| Operating Temperatures | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Cold Bend | -50°C |
| Location Rating | Class I, II, and III, Division 1 and 2 per NEC Article 501, 502, and 503 |
| Maximum Sidewall Pressure | 1000 lbs/ft |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; UL 1072 Medium-Voltage Power Cables; UL 1569 Metal-Clad Cables; UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test; UL 2225 Cables and Cable-Fittings For Use In Classified Locations; ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE); ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable; ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV; IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test; AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
| Made in America | Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661 |
Southwire 89063689 Applications
- Wet and dry areas, conduits, ducts, troughs and trays, along with direct burial.
- Suitable for variable frequency drive (VFD) applications.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.