Southwire 95287999, Control Tray Cable 10 AWG 3C Copper XHHW-2 TC-ER 600V Black
Description
Southwire 95287999 is a 10 AWG 3-conductor control tray cable with Class B compressed bare copper conductors, cross-linked polyethylene (XLPE) Type XHHW-2 insulation and a black polyvinyl chloride (PVC) jacket. It is Type TC-ER and rated 600V.
Southwire 95287999 Technical Specs
Construction
| Conductor Size | 10 AWG |
|---|---|
| Number of Conductors | 3 |
| Strands | 7 |
| Conductor | Class B compressed bare copper per ASTM B3 and B8 |
| Insulation | Cross-linked polyethylene (XLPE), Type XHHW-2, VW-1 rated |
| Conductor Colours | Black, Red, Blue |
| Filler and Binder | Polypropylene filler |
| Jacket | Polyvinyl chloride (PVC) |
| Jacket Colour | Black |
| Type | TC-ER |
Dimensions and Weight
| Insulation Thickness | 30 mils (0.76 mm) |
|---|---|
| Jacket Thickness | 45 mils (1.14 mm) |
| Approx. Overall Diameter | 0.472 in (1.20 cm) |
| Minimum Bend Radius | 1.9 in (4.83 cm) |
| Copper Weight | 97 lbs/1000 ft (144 kg/km) |
| Approx. Weight | 166 lbs/1000 ft (247 kg/km) |
Electrical and Environmental Ratings
| Voltage Rating | 600V |
|---|---|
| Conductor Temperature | 90°C normal operation in wet and dry locations; 130°C emergency overload; 250°C short circuit |
| DC Resistance at 25°C | 1.040 |
| AC Resistance at 75°C | 1.253 |
| Allowable Ampacity, Raceway, 75°C | 35 |
| Allowable Ampacity, Raceway, 90°C | 40 |
| Other | VW-1 rated; sunlight resistant; silicone free |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 44 | Thermoset-Insulated Wires and Cables |
| UL 44 VW-1 | Vertical flame test on individual conductors |
| UL 1277 | Electrical Power and Control Tray Cables |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| ICEA S-58-679 | Control Cable Conductor Identification Method 1 Table 2 |
| ICEA S-73-532 | Standard for Control, Thermocouple Extension and Instrumentation Cables |
| ICEA S-95-658 (NEMA WC70) | Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
Southwire 95287999 Applications
- Wet and dry locations, in conduits, ducts, troughs and cable trays.
- Direct burial, and aerial installation supported by a messenger.
- Class I, II, and III, Division 2 per NEC Article 501 and 502.
- The jacket is a gas/vapor-tight polymeric sheath extruded over the core per NEC Sections 501.15(D) and 501.15(E); in a classified location the cable may need further sealing under the NEC.
- Exposed runs (TC-ER) per NEC 336.10.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.