Southwire 95517977, Medium Voltage Cable 350 KCMIL 3C Copper 5 kV 133% / 8 kV 100% NL-EPR Black PVC
Description
Southwire 95517977 is a shielded medium voltage power cable rated 5 kV at the 133% insulation level and 8 kV at the 100% insulation level, with three 350 KCMIL compressed copper conductors of 37 strands each and one 2 AWG bare copper grounding conductor. Each conductor has 115 mils of no-lead ethylene propylene rubber (NL-EPR) insulation between semi-conducting conductor and insulation shields, with a helically wrapped 5 mil copper tape shield on each phase; the cable is finished in a black PVC jacket. Maximum continuous conductor temperature is 105°C.
Southwire 95517977 Technical Specs
Construction
| Number of Conductors | 3 plus grounding conductor |
|---|---|
| Conductor Size | 350 KCMIL (per conductor) |
| Strands | 37 (per conductor) |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Conductor Shield | Semi-conducting cross-linked copolymer |
| Insulation | No Lead Ethylene Propylene Rubber (NL-EPR) |
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape with 25% overlap |
| Grounding Conductor | 1 x 2 AWG, Class B compressed stranded bare copper |
| Filler | Wax paper |
| Binder | Poly glass tape |
| Jacket | Polyvinyl Chloride (PVC) |
| Jacket Color | Black |
Dimensions and Weight
| Diameter Over Conductor (per conductor) | 0.661 in (1.68 cm) |
|---|---|
| Diameter Over Insulation (per conductor) | 0.917 in (2.33 cm) |
| Insulation Thickness (per conductor) | 115 mils (2.92 mm) |
| Diameter Over Shield (per conductor) | 0.977 in (2.48 cm) |
| Jacket Thickness | 110 mils (2.79 mm) |
| Overall Cable Diameter (approx.) | 2.388 in (6.07 cm) |
| Cable Weight (approx.) | 5,197 lbs/1000 ft (7,734 kg/km) |
Installation
| Maximum Pulling Tension | 8,400 lbs (3,810.17 kg) |
|---|---|
| Minimum Bending Radius | 16.7 in (42.42 cm) |
| Maximum Sidewall Pressure | 1000 lb/ft |
Ratings
| Voltage Rating | 5 kV at 133% insulation level / 8 kV at 100% insulation level |
|---|---|
| Conductor Temperature | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Cold Rating | -40°C cold bend and cold impact |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| ASTM B496 | Compact Round Concentric-lay-standard copper |
| UL 1072 | Medium-Voltage Power Cables |
| UL 1685 | Vertical-Tray Fire Propagation and Smoke Release Test |
| UL 2225 | Cables and cable-fittings for classified locations |
| CSA C22.2 No. 2556 / UL 2556 | Cable Test Methods |
| CSA C68.10 | Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV |
| ICEA S-93-639 (NEMA WC 74) | 5-46 KV Shielded Power Cable |
| ICEA S-97-682 | Standard for Shielded Utility Cable Rated for 5 - 46kV |
| IEEE 1202 | FT4 Flame Test (70,000) BTU/hr Vertical Tray Test |
| AEIC CS-8 | Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
| Made in America | Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661 |
Southwire 95517977 Applications
- Wet and dry locations.
- Installation in conduits, ducts, troughs and cable trays.
- Direct burial.
- Class I and II, Division 2 per NEC Article 501 and 502.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.