Southwire 95838699, Medium Voltage Cable 250 KCMIL 3C Copper 5 kV 133% / 8 kV 100% Black PVC
Description
Southwire 95838699 is a 5 kV (133% insulation level) / 8 kV (100% insulation level) shielded medium voltage power cable with three 250 KCMIL, 37-strand Class B compressed bare copper conductors and one #2 bare copper grounding conductor under a black PVC jacket. Each conductor has 115 mils of NL-EPR insulation between semi-conducting conductor and insulation shields, with a helically wrapped 5 mil copper tape shield. Wax paper filler and a poly glass tape binder sit under the jacket. It operates continuously at conductor temperatures up to 105°C, with 140°C for emergency overload and 250°C for short circuit conditions.
Southwire 95838699 Technical Specs
Construction
| Number of Conductors | 3, plus one grounding conductor |
|---|---|
| Conductor Size (each conductor) | 250 KCMIL |
| Strands (each conductor) | 37 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and B8 |
| Conductor Shield | Semi-conducting cross-linked copolymer |
| Insulation | No Lead Ethylene Propylene Rubber (NL-EPR) |
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape, 25% overlap |
| Grounding Conductor | 1 x #2, Class B compressed stranded bare copper |
| Filler | Wax paper |
| Binder | Poly glass tape |
| Jacket | Polyvinyl chloride (PVC) |
| Jacket Color | Black |
Dimensions and Weight
| Diameter Over Conductor (each conductor) | 0.558 in (1.42 cm) |
|---|---|
| Diameter Over Insulation (each conductor) | 0.834 in (2.12 cm) |
| Insulation Thickness (each conductor) | 115 mils (2.92 mm) |
| Diameter Over Shield (each conductor) | 0.894 in (2.27 cm) |
| Overall Jacket Thickness | 110 mils (2.79 mm) |
| Cable Overall Diameter (approx.) | 2.209 in (5.61 cm) |
| Cable Weight (approx.) | 4,060 lbs/1000 ft (6,042 kg/km) |
Installation Limits
| Maximum Pulling Tension | 6,000 lbs (2,721.55 kg) |
|---|---|
| Minimum Bending Radius | 15.4 in (39.12 cm) |
| Maximum Sidewall Pressure | 1000 lb/ft |
Ratings
| Voltage Class / Insulation Level | 5 kV at 133% insulation level / 8 kV at 100% insulation level |
|---|---|
| Conductor Temperature | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
When CSA listed, the cable is rated at -40°C for cold bend and cold impact and marked LTGG.
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 1072 | Medium-Voltage Power Cables |
| UL 1685 | Vertical-Tray Fire Propagation and Smoke Release Test |
| UL 2225 | Cables and cable-fittings for classified locations |
| CSA C22.2 No. 2556 / UL 2556 | Cable Test Methods |
| CSA C68.10 | Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV |
| ICEA S-93-639 (NEMA WC 74) | 5-46 KV Shielded Power Cable |
| ICEA S-97-682 | Standard for Shielded Utility Cable Rated for 5 - 46kV |
| IEEE 1202 | FT4 Flame Test (70,000) BTU/hr Vertical Tray Test |
| AEIC CS-8 | Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
| Buy America | Made in America; compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661 |
Southwire 95838699 Applications
- Wet and dry locations.
- Installation in conduits, ducts, troughs and trays.
- Direct burial.
- Class I and II, Division 2 per NEC Article 501 and 502.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.