Southwire CL4Z182S0601, CL4SS™ Class 4 Cable 18 AWG 2 Pair Copper Shielded White
Description
Southwire CL4Z182S0601 is a CL4SS™ Class 4 cable built from 2 twisted pairs of 18 AWG Class B or C stranded, soft-drawn bare copper, with an aluminum foil shield, in a white lead-free, flame-retardant, low-smoke (LS) polyvinyl chloride jacket. It carries the CL4Z/CMG type designation, with a normal operating temperature of 90°C, a temperature range of -40°C to 90°C, and a rated use in dry or wet locations.
Southwire CL4Z182S0601 Technical Specs
Conductors and Construction
| Conductor Size | 18 AWG |
|---|---|
| Number of Pairs | 2 |
| Strands per Conductor | 19 |
| Conductor | Class B or C stranded soft-drawn bare copper per ASTM B3 and B8 |
| Diameter Over Conductor | 0.045 in (0.11 cm) |
| Insulation | Twisted pairs, lead-free, flame-retardant polyvinyl chloride (PVC) |
| Insulation Thickness | 17 mils (0.43 mm) |
| Shield | Aluminum foil shield |
| Jacket | Lead-free, flame-retardant, low-smoke (LS) polyvinyl chloride (PVC) |
| Jacket Color | White |
| Jacket Thickness | 25 mils (0.64 mm) |
Dimensions and Weight
| Nominal Outside Diameter | 0.349 in (0.89 cm) |
|---|---|
| Nominal Total Weight | 26 lbs/1000 ft (39 kg/km) |
| Minimum Bend Radius | 1.4 in (3.56 cm) |
Electrical and Ratings
| DC Resistance at 25°C (ohms/1000 ft) | 6.669 |
|---|---|
| Normal Operating Temperature | 90°C |
| Temperature Range | -40°C to 90°C |
| Rated Use | Dry or wet locations |
Compliance and Standards
| Type Designation | CL4Z/CMG |
|---|---|
| NEC Reference | Article 726 (2023 NEC), Class 4 circuits |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; UL 1400-2 Fault-Managed Power Systems - Part 2: Requirements for Cables; UL 444 Communications Cables |
Southwire CL4Z182S0601 Applications
- Fault Managed Power Systems (FMPS), remote powering and indoor Class 4 circuits per 2023 NEC article 726.
- Primarily agriculture, intelligent buildings and wireless densification.
- Class 4 circuits supplied from a power source (transmitter) with a voltage output of 450 volts (peak or DC) or less.
- Type CL4Z: outdoor use only, not to be attached to or used within a building structure.
- Type CMG: installation in buildings according to NEC article 722.135 and table 722.135(B).
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.