Southwire G40006-50A, Fire Alarm Cable 18 AWG 2C Solid Copper FPLP Shielded Blue
Description
Southwire G40006-50A is an 18 AWG, 2-conductor plenum fire alarm cable with solid bare copper conductors, Low Smoke Polyvinyl Chloride (LS-PVC) insulation and a blue LS-PVC jacket. It is UL 1424 Listed FPLP and carries the CMP/CL3P/FPLP type designation. An aluminum foil shield with a 24 AWG tinned copper drain wire covers the conductors. The conductors are black and red, and a rip cord is provided for ease of jacket removal.
Southwire G40006-50A Technical Specs
Conductors and Insulation
| Conductor Size | 18 AWG |
|---|---|
| Number of Conductors | 2 |
| Conductor | Solid bare copper per ASTM B3 |
| Conductor Colors | Black, Red |
| Diameter Over Conductor | 0.040 in (0.10 cm) |
| Insulation | Low Smoke Polyvinyl Chloride (LS-PVC) |
| Insulation Thickness | 10 mils (0.25 mm) |
Shield, Jacket and Dimensions
| Shield | Aluminum foil shield |
|---|---|
| Drain Wire | 24 AWG tinned copper drain wire per ASTM B33 |
| Jacket | Low Smoke Polyvinyl Chloride (LS-PVC) |
| Jacket Color | Blue |
| Jacket Thickness | 15 mils (0.38 mm) |
| Rip Cord | For ease of jacket removal |
| Nominal Outside Diameter | 0.152 in (0.39 cm) |
| Minimum Bend Radius | 0.9 in (2.29 cm) |
| Approximate Weight | 18 lbs/1000 ft (27 kg/km) |
| Copper Weight | 11 lbs/1000 ft (16 kg/km) |
Electrical and Temperature
| DC Resistance at 25°C (ohms/1000 ft) | 6.669 |
|---|---|
| AC Resistance at 75°C (ohms/1000 ft) | 8.035 |
| Operating Temperature | 0°C to 75°C |
Compliance
| Type Designation | CMP/CL3P/FPLP |
|---|---|
| Application | Fire System |
| Standards | UL 1424 Cables for Power-Limited Fire-Alarm Circuits; UL 13 Power-Limited Circuit Cables; UL 444 Communications Cables (22 AWG - 16 AWG); ASTM B3 Soft or Annealed Copper Wire; ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire; NFPA 70; NFPA 101, NFPA 130, and NFPA 502; RoHS-2 (European Directive 2011/65/EU) |
Southwire G40006-50A Applications
- Fire protective signaling circuits under Article 760 of the NEC.
- Smoke detectors, voice communications, audio control and initiating circuits.
- Installation in plenum spaces.